Study about Insulating Properties of 10 Kv XLPE Damp Cable

YUAN Ye,CHEN Jian,JIA Zhidong,LU Guojun,FAN Weinan,GUAN Zhicheng
DOI: https://doi.org/10.13335/j.1000-3673.pst.2014.10.040
2014-01-01
Abstract:With the advance of urbanization in China, cables are gradually replacing the overhead line and have been widely used in urban distribution network. However, with the rapid growth of cables in distribution network, cable faults are also increasingly frequent. The operating environment of most cables is relatively rigorous and part of connectors are always located in a humid place, or even directly immersed in water. Subsequently, the inside of cables is so easy to damp, eventually leading to insulation faults. In this paper, a heating cycle voltage test platform was designed and three serious damp 10 kV XLPE cables were selected. The heating cycle voltage test was used to heat the damp cables, making moisture discharge. The operating characteristic curves of damp cables as well the effect of moisture on operating parameters were obtained by measuring insulation resistance, dielectric loss tangent during different periods of heating cycle voltage test.