Thermal performance test and analysis of curtain-wall form solar heating system

Jie Deng,Xudong Yang,Pengsu Wang
2014-01-01
Abstract:With a demonstration project,tests the thermal performance of the curtain-wall form solar heating system.In the test period from January 7 to 9 in 2013,mean outdoor temperature is -7.7 ℃,the average collecting efficiency of the solar energy collection system is about 27.5%,and the average COP of heat pump as subsidiary heat source is 1.554.In the test period from March 13 to 15,mean outdoor temperature is 3 ℃,and the average COP of heat pump is 1.782.The test result of March 13th shows that the effective mean thermal efficiency of the solar energy collection system is 18.8%,and the heat loss of water tank and pipeline is comparatively less,which only takes 9.16% of effective heat collection of solar energy.When the terminal fan-coil adopts the air distribution mode of air supply downward from side, indoor heating effect is better.