Performance research of the PVT-coupled water loop heat pump system

Weitao Liu,Xunda Zhang,Cuishuang Guo,Dengxin Ai,Baoquan Yin
DOI: https://doi.org/10.1088/1742-6596/2584/1/012010
2023-09-28
Journal of Physics Conference Series
Abstract:Based on one public office building retrofit project in Tianjin, this paper describes the construction of a PVT coupled with a water-to-water heat pump system to test its performance in cold regions. The system's performance was evaluated under winter conditions, including the temperature changes of the photovoltaic panel and water tank with respect to the irradiation time, the instantaneous power generation of PVT and PV systems, the daily power generation efficiency, the heat collection efficiency of PVT system, and the COP of the system. The results show that under one day's solar radiation, the mean temperature of the PVT and PV systems can reach 16.1°C, and the PVT power efficiency is 2.2% higher than the PV. The PVT system has a daily average power generation efficiency of about 10.4%, a heat collection efficiency of 42.2%, and a daily power generation of 194.4 kWh. The maximum temperature of the storage water tank reached 46.4°C, and the mean COP for the whole day was 6.86, meeting the actual heating requirements.
What problem does this paper attempt to address?