Study on the Influence of Speed in DRM of SF6 Circuit Breaker

Yakui Liu,Guogang Zhang,Hao Qin,Weipeng Liu,Jianhua Wang,Jinggang Yang
DOI: https://doi.org/10.1016/j.ijepes.2020.106067
IF: 5.659
2020-01-01
International Journal of Electrical Power & Energy Systems
Abstract:As the breaking capacity of circuit breaker depends in part on the state of contact sets, and the states can be described by the electrical resistance. However, the electrical resistance shows great differences when the closing or opening speed changes due to the fault or degradation of operating mechanism, and the differences will cause trouble to the diagnosis results inevitably. In order to achieve accurate diagnosis of the contact condition, the mechanism of resistance changing with speeds has to be studied. In the present paper, the contact resistance under different speeds is measured by DRM experimental platform, and the characteristic parameters of resistance curves are extracted to show the positive correlation between contact resistance and speeds. What follows is a finite model of contact sets used to simulate the deformation and strain under different speeds. After the simulation, the influence mechanism is discussed, and a mathematical model is proposed.
What problem does this paper attempt to address?