Risk Assessment of Commutation Failure Caused by Inrush Current Based on Multi-Principal Elements Modal Analysis

Fangbing Liu,Yufei Rao,Chenghao Li,Penghui Zhang,Zaibin Jiao,Zhenan Zhang
DOI: https://doi.org/10.1109/ei247390.2019.9062003
2019-01-01
Abstract:The inrush current generated in the process of no-load closing of transformer is not only prone to misoperation of transformer relay protection, but also has adverse effects on transformer equipment and power grid. This includes adverse effects on the commutation process of the High Voltage Direct Current (HVDC) transmission system. The main manifestation is the influence of harmonic voltage and fundamental voltage changes caused by inrush current on the commutation process of inverter's AC bus. In serious cases, it may lead to commutation failure of the HVDC system or even the continuous commutation failure. In this paper, at first, the influence mechanism of commutation failure of HVDC system caused by inrush current is discussed. On this basis, multi-principal elements model analysis method is proposed to analyze the distortion of the inverter's AC bus voltage when the no-load transformer is closed at different positions. In this paper, the DC system model is built in PSCAD/EMTDC. For the built model, the no-load closing operation is carried out at different positions of the AC grid, and the influence degree of the bus voltage of the converter station caused by each harmonic wave is calculated, and is characterized the risk of commutation failure. In addition, the relevant measurements to suppress the inrush current are simulated and analyzed. It is of great significance to further ensure the safe and stable operation of the power grid.
What problem does this paper attempt to address?