A Commutation Failure Risk Analysis Method Considering the Interaction of Inverter Stations

Weichen Yang,Shihong Miao,Shixu Zhang,Yaowang Li,Ji Han,Hanping Xu,Dongyin Zhang
DOI: https://doi.org/10.1016/j.ijepes.2020.106009
IF: 5.659
2020-01-01
International Journal of Electrical Power & Energy Systems
Abstract:In the multi-infeed HVDC system, the interaction between inverter stations is an important factor that triggers the propagation of commutation failure. This paper aims to study the interaction mechanism of inverter stations and propose a reasonable method to evaluate the commutation failure risk. Firstly, based on the modified switching function, the commutation failure component is formulated to describe the commutation process and transient characteristics of inverter station during the commutation failure. Then, the analytical calculation method is studied to reflect the commutation voltage fluctuation under the influence of AC fault and commutation failure. On this basis, the commutation failure risk is assessed by comparing each valve's maximum commutation area with the minimum commutation area required for blocking. By analyzing the commutation failure risk under different grounding impedances, it is possible to identify the critical grounding inductance that causes a remote commutation failure. Based on the multi-infeed HVDC system in PSCAD/EMTDC, the validity and accuracy of the proposed method and commutation failure component are verified.
What problem does this paper attempt to address?