Study on Dielectric Recovery Characteristic of Vacuum Interrupter after High Frequency Interruption

Yu Xiao,Yi Wu,Yifei Wu,Fei Yang,Mingzhe Rong,Yuan Wei,Sunhonghao Peng
DOI: https://doi.org/10.1109/icepe-st.2019.8928914
2019-01-01
Abstract:Middle voltage direct current distribution is a promising solution for the future electric power system for its advantage in integration of renewable energy sources and improving stability of the grid. However, the rapid rise of the short-circuit fault current and the absence of natural zero crossing makes the DC interruption a main problem of the distribution system. And, the dielectric recovery strength of the vacuum interrupter is a critical factor to improve the capacity and reliability of the interruption. In order to measure the dielectric recovery strength of the vacuum interrupter, an experiment circuit is designed in this paper to measure the recovery strength of the interrupter. The recovery strength of interrupter with axial magnetic field (AMF) contacts and butt contacts are compared. The results show that the difference of recovery strength between AMF contacts and butt contacts is not so significant in small current (2kA). Whereas in large current (10kA), recovery strength of the butt contact decrease distinctly compared with AMF contact. According to the images of arc in butt contacts, it’s concluded that the arc of butt contact is gathering under large current, and the metal droplets are seriously spraying, which leads to worse dielectric recovery characteristic.
What problem does this paper attempt to address?