Abstract:In the DC grid, fault current rises very fast due to low impedance. Fast DC circuit breakers are needed to isolate faults and avoid a collapse of the common DC grid voltage. Based on the forced current zero technology, the vacuum interrupter (VI) equipped with fast electromagnetic repulsion mechanism is a very promising solution of fast DC interruption. This paper presents experimental research work on DC interruption characteristics of a vacuum interrupter. The post-arc current and transient interruption voltage (TIV) are measured with a current zero (CZ) diagnostic system. The influence of the breaking current, di/dt, rise of rate of initial TIV (RRITIV) after CZ and electrode separation on the post current have been analyzed.