Numerical Analysis on the Load Reduction of a Pipe-Embedded Window with Different Water Temperatures and Structures under Different Climates

Sihang Jiang,Xianting Li,Weihua Lyu,Shuai Yan
DOI: https://doi.org/10.1080/23744731.2019.1642094
2019-01-01
Abstract:Pipe-embedded windows can significantly reduce the cooling/heating load of buildings when integrated with low-grade energy. However, the studies on the load reduction effect under different climates remain insufficient, and the optimal location of double-glazing glass and the width of the air interlayer have not been studied. Thus, in this study, the performance of a pipe-embedded window with different water temperatures under different representative climates and structures is investigated numerically. According to the simulation, a linear relationship is found between the load and the climatic parameters with the specific structure of the pipe-embedded window, and the water temperature has a greater effect on the load than the outdoor air temperature. For three typical weather conditions from cold to hot environments (summer: 26 degrees C, 200 W/m(2); 30 degrees C, 400 W/m(2); 34 degrees C, 600 W/m(2); winter: -25 degrees C; -10 degrees C; 5 degrees C), the limits of water temperature under a 25% load reduction rate are 27.7 degrees C, 39.8 degrees C, and 51.8 degrees C for summer and 8.4 degrees C, 12.0 degrees C, and 15.6 degrees C for winter, respectively. Internal thermal insulation is recommended for a pipe-embedded window, and the air interlayer thickness and pipe location have almost no influence on the performance of the pipe-embedded window.
What problem does this paper attempt to address?