Modeling and Calculating the Power Frequency Magnetic Field of the Substation Based on the Method of Moments

LI Yongming,LUO Peng,XU Luwen,FU Zhihong
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2015.16.027
2015-01-01
Abstract:In this paper, based on the method of moment, the distribution of the power frequency magnetic field at normal operation and short circuit faults in 500 kV substation is studied. Firstly, the power frequency magnetic field moment method is proposed, then based on the models of the substation 500 kV switch yard, 220 kV switchyard, 35 kV area and the dry hollow reactor, and the power frequency magnetic field inside the 500 kV substation is analysis. The calculated results and the measured data are in good comparing, showing the feasibility and correctness of the model and algorithm; finally, the distribution of power frequency magnetic field below the incoming lines in substation 220 kV regional at the single phase short circuit fault is analysis. The work of this paper, which can provide the distribution of power frequency magnetic field in different conditions in the substation, and also is an effective method to forecast the distribution of power frequency magnetic field in substation.
What problem does this paper attempt to address?