A Calculation Method of Fault Current Distribution and Shunt Coefficient in Substation Based on Phase-coordinate Model

吴锦鹏,张波,蒋愉宽,曾嵘,何金良
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2012.01.018
2012-01-01
Abstract:While a short circuit fault happens in a power substation, it is the current diffusing into ground that actually causes the safeness trouble instead of the fault current. Most of the current numerical methods and software are required to cross the technical threshold, or have limitations in characterizing the power system. The paper presented a numerical method to calculate the shunt coefficient for the complex power system with different voltage levels, and derived the admittance matrix for a phase-coordinate transformer model which is applicable for the loop current method. The method was verified by comparison with commercial software CDEGS. It has been applied to analyzing the effect of the transformer, and the result shows that the transformer is an essential system component for the calculation of shunt coefficient.
What problem does this paper attempt to address?