High Voltage Ride-through Control Strategy of Grid-connected Inverter for Renewable Energy Systems

Zhong ZHENG,Hua GENG,Geng YANG
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2015.06.022
2015-01-01
Abstract:Grid voltage swell will reduce the control margins of grid-connected inverter (GCI) for renewable energy systems, and the uncontrollability of GCI could lead to the reversal of power flow in the inverter which may result in over-voltage of the DC-link capacitors or over-current of the inverter. In order to relieve the transient impacts on GCI caused by grid voltage swell and ensure the safe grid-connected operation of GCI, a new high voltage ride-through (HVRT) control strategy of the GCI was presented. In this paper, the controllability of GCI considering its rating limitation was firstly analyzed, and the corresponding controllable regions for different grid voltage swell ranges were also discussed. After that, an adaptive adjustment algorithm of the DC-link voltage reference was designed by means of the information of grid voltage and the load current of GCI, so that the GCI can always remain controllable. At last, combining with the control of GCI’s inductive reactive current, the whole HVRT scheme of GCI was proposed. The accuracy of calculated GCI’s controllable regions and the effectiveness of proposed control strategy for GCI during grid voltage swell were both validated by the simulated and experimental results.