Short Circuit Current Characteristics and Calculation of Current Protection Setting of Feeder Lines in Wind Farms Considering LVRT

Han WU,Jianlong SUN,Liwei QIAO,Ying QIAO,Zongxiang LU,Jiayang RUAN
DOI: https://doi.org/10.13335/j.1000-3673.pst.2016.10.014
2016-01-01
Abstract:Current protection settings of feeder lines in wind farms prefer higher sensitivity and lower selectivity,mismatching low voltage ride through (LVRT).This paper deduced short circuit current formula and characteristics in doubly fed induction generator considering LVRT with crowbar switched on.According to IEC 60909,key factors of short circuit current in feeder lines of wind farms were discussed with equivalent voltage source method.Variable curve of short circuit current of faulted feeder line in different fault locations or grid intensities were depicted.A new current protection setting scheme of feeder lines was proposed.Based on model simulation results,a calculation example of the new scheme was accomplished.
What problem does this paper attempt to address?