Short circuit current calculation method of power system integrated with DFIG based on equivalent sequence circuits

Jinhua ZHANG,Baohui ZHANG,Linhao CHEN,Zhiguo HAO
DOI: https://doi.org/10.16081/j.issn.1006-6047.2018.01.003
2018-01-01
Abstract:To calculate the short circuit current distribution in power system integrated with DFIG(Doubly-Fed Induction Generator) conveniently and accurately,the rotor speed frequency and power frequency equivalent sequence circuits of DFIG with Crowbar protection are proposed,based on which,a short circuit current calculation method of the system is given.The analytic expressions of power frequency component and rotor speed frequency component of DFIG flux linkage are obtained by solving the state differential equation of DFIG flux linkage with Crowbar protection.Based on this,the space vector equation of DFIG voltage is decomposed into rotor speed frequency and power frequency components,to obtain the equivalent sequence circuits for rotor speed frequency and power frequency respectively according to the relationship between space vector and phasor.The negative and positive sequence equivalent circuits of rotor speed frequency are passive impedance and electric potential with internal impedance respectively and the negative and positive sequence equivalent circuits of power frequency are both passive impedance.Based on the equivalent circuits the short circuit currents in power system integrated with DFIG can be calculated with only DFIG electric machine parameters and initial conditions of failure without simulation.The system integrated with DFIG is simulated in PSCAD to verify the effectiveness of the equivalent circuits and short circuit current calculation method with different faults in the system.
What problem does this paper attempt to address?