Proportional multi-resonance current control of grid-connected converter under unbalanced and distorted grid condition

Gang HAN,Xu CAI
DOI: https://doi.org/10.16081/j.issn.1006-6047.2017.11.017
2017-01-01
Abstract:Aiming at impacts of the unbalanced and distorted voltage on grid-connected converter performance,the proportional multi-resonance regulator is adopted to optimize the current loop.On the basis of the converter model in two-phase static axis,a dual-loop control structure with both the DC outer-voltage loop and the inner-current loop is presented.To track the reference current and suppress the voltage disturbance,the proportional multi-resonance regulator is adopted in the current loop.As for the converters with LCL filter,the order of filter and proportional multi-resonance regulator is high and the parameter design is complicated,aiming at which,a regulator parameter design method based on the root locus analysis in the discrete domain is proposed.Effects of the resonance regulator parameters on the system closed-loop poles are analyzed,based on which the control parameters of the current loop are designed to guarantee the robustness against the fluctuation in the LCL filter parameters and grid frequency.On the RT-LAB-based hardware-in-loop experimental platform,the feasibility of the current control method and the effectiveness of the proposed regulator parameter design method are verified.
What problem does this paper attempt to address?