Seismic Responses and Seismic Resistance Measure of ±800 kV Direct Current Bypass Switch

Qingqing HE,Zhenyu YANG,Qiang XIE,Yuxin LU,Ran ZHUO,Rong HU,Bangxin SUN
DOI: https://doi.org/10.13296/j.1001-1609.hva.2018.02.007
2018-01-01
Abstract:The post class equipments,which are similar to the bypass switch,have experienced severe damage in the past earthquakes.In order to study the seismic performance of the bypass switch,a finite element model,which is based on a ±800 kV direct current bypass switch,is established.The seismic analysis shows that the bypass switch could not satisfy the seismic request after combination with other corresponding loads.Then,an seismic resistance bearing system combining wire rope and viscous dampers is installed at the bottom of the bypass switch to decrease its responses.The hysteretic curve of the wire rope is simulated by a modified Bouc-Wen model,then the seismic responses of the bypass switch with and without seismic resistance are analyzed.The results show that with the seismic resistance bearing system,the stress at the bottom of the insulator is greatly decreased and the safety factor is larger than the requirement.The seismic resistance bearing here can effectively improve the seismic performance of the bypass switch.
What problem does this paper attempt to address?