Analysis on Temperature Characteristic of Flake Melt of Fuse-switch Disconnector for Distribution Transformer Protection

YANG Cuiru,WANG Wenxuan,LEI Jing,LIU Donglin,LIN Yifeng,YANG Ying
DOI: https://doi.org/10.3969/j.issn.1007-290X.2016.05.021
2016-01-01
Abstract:Refusal-operation of fuse for distribution transformer protection may cause over-load burn-up of the distribution transformer and serious accident consequence. In allusion to flake melt of fuse-switch disconnection for distribution trans-former protection,a kind of mathematical model for calculating temperature rise with change of current is established and a method for accurately calculating heat transfer coefficient of the melt is presented. It is verified that simulation result of the melt with low expansion current could be well identical to the actual condition by means of establishing 3D thermoelectric coupling model,using ANSYS software for simulation and combining with experiment on actual temperature condition of the melt. Meanwhile,it is proved to be beneficial for accurate characteristic simulation and pattern design on fuse for distribu-tion transformer protection.
What problem does this paper attempt to address?