Research on Temperature Field Simulation of Resin Insulated Dry-Type Power Transformers

YAN Han,GUO Yongji,LIN Zhaozhuang
DOI: https://doi.org/10.3321/j.issn:1000-0054.1999.07.001
1999-01-01
Abstract:The operation of cast resin dry type power transformers is mainly depended on its thermal characteristics. Based on the finite diffrence, a computerized model and software for dry type power transformers temperature field numerical simulation are proposed. The results of temperature field distribution of SC8 1000/10 transformer core, low voltage winding and high voltage winding are obtained. The corresponding field temperature rise experiment shows the consistency between simulation results and experiment data. The results show that the hottest point of low voltage windings is located in the center of bottom surface, the hottest point of high voltage winding is located below inner medium. These results give proper advice to allotcate thermocouple detector, which is available for design and operation.
What problem does this paper attempt to address?