Influence of Grading Capacitances on the Lightning Impulse Breakdown Voltage of a Double-Break Vacuum Circuit Breaker

Pei Liu,Shaowei Liu,Lixin Hong,Xiaofei Yao,Zhiyuan Liu,Yingsan Geng,Jianhua Wang
DOI: https://doi.org/10.1109/deiv.2018.8536979
2018-01-01
Abstract:The objective of this paper is to determine the influence of grading capacitances on the lightning impulse breakdown voltage of a double-break vacuum circuit breaker (VCB). A double-break VCB was built up, which consisted of two 12 kV vacuum interrupters in series. A positive lightning impulse breakdown voltage was applied with the up-and-down method, by which 50% breakdown voltage U-50 was obtained. 5 kinds of grading capacitances were considered, which included 0, 100, 500, 1500 and 5000 pF, respectively. The experimental results show that with an increase of grading capacitance, the U-50 single-break VCB decreased. However, with the increase of grading capacitance, the U-50 of the double-break VCB increased at first, reaching the maximum value at the grading capacitance of 500 pF. After that the U-50 decreased with further increase of the grading capacitance. When the grading capacitance was low, the voltage distribution of double-break VCB improved significantly with the increase of the grading capacitance. But the improvement of the voltage distribution of the double-break VCB saturated when the grading capacitance was higher than 500 pF. Comparing the U-50 of single-break VCB with the U-50 of double-break VCB at the same total contact gap, the gain coefficient increased from 1.18 with the total contact gap of 2 mm to 1.41 with the total contact gap of 8 mm.
What problem does this paper attempt to address?