Influence of moisture content on the frequency response analysis of power transformers

Li Wang,Ming Dong,Jiacheng Xie,Yizhuo Hu,Ming Ren
DOI: https://doi.org/10.1109/ICPADM.2018.8401093
2018-01-01
Abstract:Frequency response analysis (FRA) is a common method for the detection of mechanical faults in transformers. However, non-mechanical parameters can also affect the FRA of transformers. In this paper, the influence of moisture content on the FRA of a three-phase transformer was studied. Firstly, dielectric response of oil-immersed paper with different moisture contents were measured and the results were used in the simulation model of the transformer. End-to-end short circuit test and capacitive inter-winding test were employed in this paper. The influence of moisture content on the two configurations was studied by analyzing the FRA curves with correlation coefficient. Results show that for end-to-end short circuit test, the judgement result of low frequency band is more susceptible by moisture content, while for capacitive inter-winding test, the influence on the judgement results of low, middle and high frequency band is nearly the same. In addition, the influence of moisture content changing at partial region was also studied and results show that the influence is much smaller than that when moisture content of the whole transformer changes.