The Effect Of Moisture And Temperature On The Oil-Immersed-Paper Used In Ehv Converter Transformer

Hao Wu,Lilan Liu,Teqing Liu,Zongren Peng,Xiaolu Lv,Jintao Liao
DOI: https://doi.org/10.1109/icd.2016.7547670
2016-01-01
Abstract:The insulation demand of converter transformer is higher than that of ordinary transformer, due to the different functions and operating environment. In order to assess the insulation properties of converter transformer, the study of the temperature and moisture effect on the oil-immersed-paper is conducted. The research objects are weidmann 14 kraft paper (made in Taizhou, China) and Kelamayi transformer oil KI5OAX (made in Xingjiang, China), both used in EHV converter transformer. The polarization-depolarization current (PDC) and frequency domain spectra (FDS) tests are performed on the oil impregnated pressboard samples of diverse water content under different temperatures. The results show that the dielectric properties and resistivity of oil-impregnated-paper are remarkably affected by moisture content and temperature, the real part of relative permittivity and dielectric dissipation factor change significantly with temperature and moisture at frequency range of 10(-3)similar to 10(-1) Hz; the natural logarithm of sample's resistivity changes linearly with both the moisture content and the temperature. The influence of temperature should be considered when diagnosing moisture content of transformer through PDC and FDS.