An Analytical Model for Predicting the Particle-Deposited Fin Efficiency

Feilong Zhan,Dawei Zhuang,Guoliang Ding
DOI: https://doi.org/10.1016/j.ijrefrig.2018.03.021
IF: 4.14
2018-01-01
International Journal of Refrigeration
Abstract:Fins of heat exchangers are gradually deposited by dust particles in most application scenarios, and so a model of particle-deposited fin efficiency is needed for heat transfer prediction. In this study, the expression of fin efficiency for a particle-deposited annular fin was developed by simplifying the fin as two two-dimensional coating layers on a one-dimensional clean fin firstly, and then this expression was extended to rectangular fins with circular holes by the equivalent radius transformation. The analytical solutions for a typical rectangular fin show that the attenuation rate of fin efficiency may increase up to 23.9% if the fin surface is covered by a fouling layer with an average thickness of 4.0 mm. This model can be used to predict the heat transfer rate of fouled heat exchanger with multi-fins, and the validation results show that the accuracy of the proposed model is acceptable in engineering applications. (C) 2018 Elsevier Ltd and IIR. All rights reserved.
What problem does this paper attempt to address?