Arc Temperature Profile Measurement and Characteristic Analysis on an SF 6 High-Voltage CB

Su Bai,Yonggang Guan,Haiyun Luo,Weidong Liu
DOI: https://doi.org/10.1049/iet-gtd.2017.1792
2018-01-01
Abstract:The arc temperature profile in an interrupter, which determines the extinguishing characteristic of an SF6 circuit breaker (CB), is of interest to designers and developers. In this investigation, optical fibres and spectrograph were employed to measure the arc temperature profiles in a 252kV SF6 CB during short current interrupting. The temperature profiles of the upstream, throat, and downstream of the nozzle have been measured. The optical fibres can transfer the arc light from the measuring points in the nozzle to the spectrograph. Moreover, the spectral line intensities of copper (Cu) 510.5, Cu 515.3, and Cu 521.8nm were obtained by the spectrograph. The condition in CB can be treated as a local thermal equilibrium system, and the temperature profiles can be calculated by two-line method and Abel inverse method. The arc temperature profiles of the interrupter under 15-50kA root mean square current have been analysed through the method established in this investigation.
What problem does this paper attempt to address?