Mathematical Model and Energy Efficiency Analysis of a Vacuum-Based Liquid Desiccant Regenerator
Xiaohong Yin,Xinli Wang,Xinyu Wei,Hongxia Zhao,Lei Wang,Lei Jia
DOI: https://doi.org/10.1016/j.buildenv.2021.107629
IF: 7.093
2021-01-01
Building and Environment
Abstract:Liquid desiccant air conditioning (LDAC) has been considered as a promising solution for efficient air temperature and humidity control in air conditioning fields. However, the high regeneration temperature of desiccant solution impedes its spread and application. In this study, a vacuum-based liquid desiccant regenerator (VLDR) for desiccant solution regeneration in LDAC driven by low-grade energy is studied, meanwhile, the mathematical model considering the variation of heat transfer coefficient under different operating conditions is developed to analyze the system performance and energy efficiency. After the model is validated by the experimental data, the regeneration performance and energy efficiency analysis of the VLDR system is simulated and investigated. Simulation results show that hot water temperature, flowrate are the variables that affect the performance of the generator, and the performance of the condenser is influenced by cooling water temperature and flowrate. Opposite influences for vacuum pressure are found on the performances of generator and condenser, therefore the hot water temperature, vacuum pressure, and cooling water temperature should be designed properly to provide the required regeneration capacity with the pressure balance maintained. Moreover, energy efficiency is analyzed by comparing the ratio of water vapor generation rate to the total electricity consumption of the VLDR under different temperatures and vacuum pressures.