Numerical Study On Heat And Mass Transfer Of The Cross-Flow Liquid Desiccant Regenerator

Yang Li,Zhibo Fu,Xiaohu Yang,Lianying Zhang,Qunli Zhang,Wenju Hu
DOI: https://doi.org/10.1016/j.proeng.2017.10.212
2017-01-01
Abstract:Liquid desiccant air conditioning (LDAC) system becomes more and more environmentally friendly and efficient than vapor compression cooling system to control air humidity. This paper concentrates on the heat and mass transfer process of cross-flow liquid desiccant regeneration. A cross-flow theoretical model based on finite difference method was established. The LiBr aqueous solution was used as the liquid desiccant. A mass transfer empirical correlation fitted by experimental results was introduced to the model. The software MATLAB was adopted to solve the control equations. The results show the maximum differences of air temperature and humidity ratio reach 3.8 degrees C and 4.2 g center dot kg(-1) in air outlet, respectively. There exists an optimal NTUm in regenerator based on a certain operation condition. (c) 2017 The Authors. Published by Elsevier Ltd.
What problem does this paper attempt to address?