Experimental Study on Cross-Flow Regeneration Based on Small Liquid Desiccant Air Conditioner

Yakun JI,Guozhong DING,Xiang CHEN,Yongzhen LI
DOI: https://doi.org/10.3969/j.issn.1674?2869.2018.02.022
2018-01-01
Abstract:The cross-flow regeneration experimental equipment was set up based on the small liquid desiccant air conditioning system.The Celdek structured packing was chosen as the heat and mass transfer medium,LiCl was served as regenerant,and the regenerated capacity was selected as the evaluation criteria for system performance. The effects of liquid desiccant flowrate,liquid desiccant inlet temperature,air flowrate and air inlet temperature on the performance of the regenerator were fully studied. The conclusion was that:under the condition of miniaturization,the regenerated capacity increased with the growth of solution flowrate,liquid desiccant inlet temperature and air flowrate;while air inlet temperature had little effect on the regenerated capacity.Moreover,the correlation formula of mass transfer coefficient about miniaturization system was fitted, and it was adapted to compare the experimental values with calculated values,the results showed that the deviation of each parameter was controlled within the range of 9%,which indicated that the fitted correlation formula had a good performance.
What problem does this paper attempt to address?