Fast Loop Closing-Opening Operation of Two Lines with 30 Degree Phase Difference

Xiang Wei,Zhang Jianmin,Luo Gang,Jin Naizheng,Xie Dong
DOI: https://doi.org/10.1109/chicc.2016.7554929
2016-01-01
Abstract:In case of upstream main power transformers using different winding connection modes like Y/Y/Y vs Y/Y/Δ, two incoming lines of substation or two feeders of electrical distribution network might have 30 degree angle difference, therefore a large amount of loop current approximately about one fourth of short circuit current will be produced when they are connected in loop, so it is strictly prohibited according to present operation rules, which means load transferring between them is impossible without power cut, consequently being against the uninterruptible power supply for the most important customers. This paper puts forward a new proposal to have a fast loop closing-opening sequence operation of two corresponding breakers of those two lines or two feeders, under the predicted a tolerable loop current value with a tolerable heat effect on the looped electrical equipment and impacts on connected customer's electrical appliances, as well as the parameter setting coordination or interlock of related protection relays to avoid the possible interruption of power supply.