Fault Reconfiguration of Super Uninterruptible Power Supply

Yixiang Fang,Hao Wang,Haijin Li,Changsheng Hu,Dehong Xu
DOI: https://doi.org/10.1109/ipemc.2016.7512870
2016-01-01
Abstract:Super Uninterruptible Power Supply (Super UPS) is composed of multiple energy sources. The critical goal of fault reconfiguration for Super UPS is to ensure high reliable power supply to the load. Firstly, fault reconfiguration modes of Super UPS at different source faults are discussed. Secondly, seamless transfer for the source fault are presented. Instead of waiting for the central controller command of the Super UPS, the super capacitor module detects the base source fault by indirectly detecting the sag of the DC bus voltage. Once the super capacitor module detects the fault, it will changes from the charge mode to voltage control mode to take over DC bus voltage temporarily before the new base source module finishing the startup. Therefore, it guarantees the uninterruptable load power without depending on delayed communication line. Finally, the fault reconfiguration is verified by the experiment.
What problem does this paper attempt to address?