Simplified formula for calculating grounding resistance of grounding system using tunnel foundation in cable tunnel

Xue-long DU,Tian-jiao QIU,Xiao-ying ZHANG,Xue-liang MA,Fan YIN,Jian GUO,Jun ZOU
DOI: https://doi.org/10.3969/j.issn.1003-3076.2014.11.007
2014-01-01
Abstract:The grounding resistance is one of the important parameters for the safe operation of the grounding system in cable tunnel.Based on the simulation analysis,a simplified formula for calculating the grounding resistance of grounding system using the tunnel foundation(GSTF) is provided in this paper.Firstly,the simplified grounding system of cable tunnel is obtained and the corresponding finite element simulation model is built.Then,the influence of the number of steel bar layer,the number of steel bar,the conductivity of cement layer and the thickness of cement layer on the grounding resistance is analyzed.At last,according to the simulation results,the problem that solving the grounding resistance of the complex grounding system in tunnel can be simplified to that solving the grounding resistance of the buried cylindrical conductor whose grounding resistance can be obtained easily.The results indicate that the accuracy of the simplified formula can meet the needs of engineering calculation.And the expression is suitable for calculating the grounding resistance of GSTF in cable tunnel.
What problem does this paper attempt to address?