Insulation co-ordination researching for power cable in Traction Substation

Liu Ming
2002-01-01
Abstract:The input Voltage of traction supply system is 220 kV for the electrified railway Haerbin Dalian. The transmission line to traction substation Wanggang uses union method of 220 kV XLPE cable and head line. There is not only precedent, but also not design codes for the mode of power supply in China. In order to choose insulation level of the cable, possible lightning and switching overvoltage are calculated in this paper. Results of calculation indicate that biggest switching overvoltage is 458 kV, and biggest lightning overvoltage is 1 349 kV. Referred to national and international related standards and literatures, it is devised that the protecting measures of adopting independent lightning rod, reducing tower's grounding resistance, adding zinc oxide lightning arrester. On the base, the insulation co ordination methods for the cable are put forward.