Application of Distributed Optical Fiber Sensing Technology to Temperature Monitoring of Buried Pipes of Ground Source Heat Pump System

Junqiang QI,Baojun WANG,Bin SHI,Xing WANG
DOI: https://doi.org/10.13409/j.cnki.jdpme.2015.06.009
2015-01-01
Abstract:In this paper,the experimental model of the ground source heat pump central air-conditioning system was established.With this system,the heat transfer performance of the ground source heat pump system was discussed.The temperature data in the deep region was acquired through distributed fiber optic sensing technology.The results demonstrate that the constant temperature zone is 45 mbelow the surface,and the constant temperature is 18℃.The research on the heat transfer performance both in summer and winter demonstrate that the systemu0027s performance is related to the input water temperature and the differential temperature between stratums,and the higher the input water temperature and more differential temperature between stratums,the better heat transfer performance is.The temperature drop range in winter and summer is more than 4.5℃and 2.2℃respectively.According to the monitoring result,the soil is capable of strong temperature self-balanced ability,but after the disturbance,it needs a relatively long compensation process to recover.So usage of ground source heat pump should take a full consideration of the heat balance in warm and cold season.The pipeline on the ground has an obvious effect on the heat transfer performance of ground source heat pump,so we should also take a full consideration on the insulation performance of the over ground part.
What problem does this paper attempt to address?