Study on the Heating and Humidification Performance of Desiccant Coated Heat Exchanger System in Winter

Jing-Yu ZHANG,Tian-Shu GE,Yan-Jun DAI,Yao ZHAO,Ru-Zhu WANG
2017-01-01
Abstract:In this paper,a desiccant coated heat exchanger system is installed and tested under typical winter condition at Shanghai.Effects of hot water temperature,hot water mass flow rate and regeneration air flow flux are discussed as vital factors impacting system performance.It is found that the optimum regeneration hot water temperature and mass flow rate is 40℃ and 0.4 kg/s,when the regeneration air mass flow flux is 400 m;/h.Under this operation condition,average humidity ratio of supply air is 5.15 g/kg,and COP; can reach 1.78.For different humidify ratios of ambient air,a strategy of appropriate mass flow fluxes of air is implemented to balance thermal comfort and system thermal efficiency.
What problem does this paper attempt to address?