Design and Performance Analysis of Open Loop River Water Source Heat Pump System

yu xin,li rui,dai yanjun
DOI: https://doi.org/10.3969/j.issn.2095-4468.2015.02.109
2015-01-01
Abstract:The operation performances of water-to-water heat pumps using river water as the heat source and sink were investigated. The system test-bed was constructed in Sino-Italy green energy laboratory in a campus in Shanghai. An initial experiment was carried out on the quality of river water. The results indicate that the water should not go through the heat pump directly. The river water source heat pump system and performance testing system were designed, and then the system performances in a typical summer day and a typical winter day were investigated and analyzed. The results indicate that the system COP in the typical summer day and COP in the typical winter day are 5.2 and 3.1, respectively.