Application design of electronic transformer with distributed structure in the measurement of furnace transformer's large current

Zhi-guo TIAN,Zhi-yuan LIU,Shao-peng WEI,Ding PAN
DOI: https://doi.org/10.3969/j.issn.1000-7059.2017.02.012
2017-01-01
Abstract:The low-voltage side of the furnace transformer current can reach up to tens or even hundreds of kilo-ampere,so it needs to be output though a plurality of independent parallel conductor.The size of conductor is very large,and there is no suitable high precision transformer to measure this current at present.By considering the Rogowski coil characteristics of non-magnetic-saturation and wide measurement range,a distributed electronic current transformer using the block module installation structure,combining with branch structure of low-voltage side conductor in electric furnace transformer,is designedto solve the problem of large current accurate collection.Test result shows that this design has high accuracy and convenient installation,which can fully meet the needs of ultra large current measurement for electric furnace transformer.
What problem does this paper attempt to address?