Application of S Transform for Time-Frequency Analysis of Partial Discharge Signals in Power Cables

Guo Canxin,Yong Ming,Xu Minhua,Li Qing,Yao Linpeng,Qian Yong,Huang Chengjun,Jiang Xiuchen
DOI: https://doi.org/10.19595/j.cnki.1000-6753.tces.2010.11.002
2010-01-01
Abstract:For partial discharge detection in power cables, a new-type S transform time-frequency analysis method is introduced to distinguish the partial discharge signals from field noise. Partial discharge signal is a typical non-stationary signal, and its characteristics can not be clearly expressed only by time-domain or frequency-domain information. S transform is a combination and extension of continuous wavelet transform and short time Fourier transform (STFT). The S transform method employs a Gauss window, whose amplitude and width change with frequency. S transform achieves better time resolution in high frequency proportion, and better frequency resolution in low frequency proportion. Compared with traditional time-frequency representation like STFT and Gabor transform, the S transform is used to analyze the simulation and on-site detection signals from power cables earthing strap. The results show that S transform is effective in extracting partial discharge characteristic information.
What problem does this paper attempt to address?