Influence of the Source and Sink Temperatures on the Experimental Research of A Co2 Trans-Critical Refrigeration and Heat Pump System

Zhang Wen-hui,Wang Zhe,Gong Yi,Wu Xue-hong,Lu Yan-li
DOI: https://doi.org/10.4028/www.scientific.net/amr.614-615.682
2013-01-01
Abstract:The performance of the CO2 trans-critical system is affected significantly not only by optimal system pressure but also by instantaneous ambient temperatures. This paper presents the results of a study carried out to elucidate the influence of the source and sink temperatures on the experimental research of a CO2 trans-critical refrigeration and heat pump system which used a new dual expansion valve and a balance CO2 liquid receiver adjustment device. The unit had been fully tested along a multistate experimental study, at various evaporating temperatures and different gas cooler outlet pressures. The results showed that: the source and sink temperatures rose from 15°C to 25°C, trans-critical CO2 systems COPH average increase of 4.4% each 5°C, but COP decrease of 6.8%. The influence of the source temperature on the chilled water outlet temperature which is less than the sink temperature. The effect of the source or sink temperature on the cooling water outlet temperature to average every 5°C to change the range of from 0.7°C to 1.9°C.
What problem does this paper attempt to address?