Influence of Power System Voltage Drop on the DIFG Shaft

Meng-zeng CHENG,Jian-wen ZHANG,Xu CAI,Yun-feng CAO
DOI: https://doi.org/10.3969/j.issn.1674-3415.2011.20.004
2011-01-01
Abstract:To study the influence of power system voltage drop on the doubly-fed induction generator(DIFG) shaft,this paper analyzes the electromagnetic torque change within DFIG through approximated analytical expression of stator fault current and rotor fault current obtained by the superposition between transient current based on vector method and steady state current based on equivalent circuit method,and then through the analytical expression of DFIG torque under the following circumstances:stator terminal three-phase symmetrical voltage dip,the rotor side converter are cut off,and the crowbar circuit is put into the operation.Furthermore,a 2MW DFIG model is established by PSCAD based on theory analysis,and the simulation results validate that torque changes of DFIG shaft could be analyzed by the analytical torque expressions of DFIG during grid fault.At last,the optimizing value of Crowbar resistance is given.