Research on Tie Line Power Flow Oscillation in Weak Interconnection Power Grids

HONG Feng,CHEN Jinfu,DUAN Xianzhong,XI Jianghui,LING Weijia,Ll Yong,JIANG Man
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2011.10.009
2011-01-01
Abstract:The peak value of tie line oscillation power in the weak interconnection bulk power grids following large disturbances (generator tripping, DC blocking) was discussed based on the interconnected power system of North China and Central China. The characteristics of tie line oscillation were analyzed based on the real power grid. The maximum oscillation power value was deduced on two-machine system and analyzed the relative factors of influencing the power peak value of the tie line. It's pointed out that the peak value of oscillation power is proportional to the abrupt change of electromagnetic power and is inversely proportional to the ratio of the rotational inertia of the fault grid to the other side grid. The difference of abrupt change of electromagnetic power is closely related with the location of faults, therefore, the closer the distance between the fault location and tie line impact point, the smaller the transfer ratio. The conclusions were verified by the calculation results of the measured data of the tie line of North China and Central China interconnected power system. © 2011 Chinese Society for Electrical Engineering.