Finite Long Body Source Model of Tube Group after Long-Time Heat Exchange in Ground Source Heat Pump

ZHAN Guo-hui,ZHANG Yi-ping,XU Jian,YU Ya-nan
DOI: https://doi.org/10.3785/j.issn.1008-973x.2011.08.014
2011-01-01
Abstract:Thermal field after a long-time running was studied in order to further improve the accuracy and the simplicity of analytical model for the ground source heat pump tube group system.According to the existed finite length cylinder source model of single tube,the error of the rising temperature outside the cylinder between the finite length cylinder source model and the finite length line source model is negligible when the radius of the cylinder is not larger than the critical value.Based on this finding,the finite length body source model of tube group system was built by replacing the line source model with the cylinder source model in the existed superposition method.The finite length body source model has the same accuracy but the amount of calculation is obviously reduced by comparing with the line source superposition method and the finite element method.The difference between the finite length body source model and the line source superposition model was analyzed for different arranged form of the tube group system,and the result shows that the difference increases slightly as the difference of volume approximation increasing.
What problem does this paper attempt to address?