Feasibility Analysis of Metalized Membrane Method Applied to Monitor Corona Loss of Transmission Lines

张琪,刘海沧,罗勇芬,张源斌,吴健,白晓春
DOI: https://doi.org/10.13336/j.1003-6520.hve.2011.10.018
2011-01-01
Abstract:The metalized membrane method, in which transmission line was coated by metalized membrane where the insulated layer was next to transmission line and mental layer was outwards, was applied to monitor the corona losses on AC/DC transmission lines online. The sampling resistance between transmission line and membrane could convert leakage current to voltage signal which would be sent to a computer by wireless telecommunications way or optical fiber transmission way. The voltage of transmission line would also be sent to a computer after converting by PT or voltage divider. The leakage current, corona loss, and other data could be calculated by a prepared program on the computer. The measurement results of the leakage current of the metalized membrane and the leakage current on the sampling resistance at the beginning of the transmission were compared, and the related coefficient, time de- lay and unit length leakage current were analyzed. Results prove that this new method is feasible to measure corona losses, and easy to realize monitoring online. This method can be practically applied to not only on-load and no-load lines, but also AC and DC transmission lines.
What problem does this paper attempt to address?