Effect of Corrosive Factors in the Regenerated Water on Stainless Steels of Condenser Tube in Power Plant

ZHANG Wan-you,ZHOU Ding,LI Jin
2010-01-01
Abstract:This paper demonstrated the reuse of secondary drainage water treated by the membrane bioreactor and weak acid ion exchange resin from sewage treatment plants in circulating cooling water systems of power plants. For the water quality characteristics, the methods of electrochemistry, orthogonal experiment, and surface image analysis technique (scanning electron microscope, SEM) were employed to study the erosion of the main factor in medium, including ammonia concentration, chemical oxygen demand (COD) concentration, and medium pH on 316L stainless steels of condenser tubes. The results show that under the test conditions, when the ammonia concentration grows above 18 mg/L, a significant impact on the corrosion resistance of 316L stainless steels electrode surface will occur, and the electrode pitting potential of 316L stainless steels will decrease significantly. At the same time, the SEM observation reveales that after the electrode surface reaching the breakdown potential, the electrode surface will form large pieces of black corrosion spot. As the medium pH ranges from 8.3 to 8.5, values of COD300 mg/L and NH+4-N5 mg/L have no significant effect on the corrosion resistance of 316L stainless steels.