Comparison of Microbiologically Induced Corrosion on Metals in Industrial Recycling Cooling System Makeup by Municipal Reclaimed Water

Xu Ping,Wang Jin,Zhang Yajun,Xu Zhaoyi,Liu Xiaodong,Liu Ting
2013-01-01
Abstract:Compared with surface water,there are more organics,nitrogen,phosphorus and microorganisms in municipal reclaimed water,It is necessary to research microbiologically induced corrosion(MIC)in industrial recycling cooling water system makeup by municipal reclaimed water.For recycling cooling water system makeup by municipal reclaimed water,MIC of stainless steel,brass and carbon steel in the sterile and non-sterile real water is studied and compared by electrochemical method,corrosion coupons experiment and scanning electron microscope.The main parameters are fitting resistance(solution resistance,biofilm resistance and polarization resistance),corrosion potential,corrosion current and corrosion rate.The results show that the corrosions of three metals are all exacerbated in nonsterile water,with the MIC of stainless steel the most serious and that of brass the least serious.The impacts of microorganism on the corrosion behavior of stainless steel,brass and carbon steel are significantly different.Microorganism has no influence on the variation of corrosion behavior of stainless steel and carbon steel with time,but its impact on brass corrosion behavior is significant.