Penetration Level Permission of for DG in Distributed Network Considering Relay Protection

WANG Jiang-hai,TAI Neng-ling,SONG Kai,GU Lin-feng,SHENG Ji-qing
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2010.22.004
2010-01-01
Abstract:The distributed generators (DG), connecting with the power system through the distribution network (DN), can cause the change of the detected current for protection relay and the protection coverage. The maximum allowable capacity of the distributed generators in the DN was analyzed for meeting the requirements of relay protection and limiting the impact to short-circuit current characteristics. The influence factors of the maximum allowable capacity including the connection location, the composition of multiple DG and the line parameters in the DN were also analyzed. Analysis results show that the accessing capacity of DG is small if the original DN protection configuration is not improved. To solve this problem, some measurements, with only a small number of changes to the original DN protection, were proposed to effectively improve the penetration level. Finally, the effectiveness of the measure was verified by analyzing a 10 kV distribution system. © 2010 Chin. Soc. for Elec. Eng.