Research on the impact of DG capacity on the distribution network current protection and countermeasure
Xi-ke FENG,Neng-ling TAI,Kai SONG,Lin-feng GU,Ji-qing SHENG
DOI: https://doi.org/10.3969/j.issn.1674-3415.2010.22.030
2010-01-01
Abstract:When short circuit fault occurs in the transmission line of distribution network with DG connected, the injection current of the distributed generation may have an impact on the short circuit current, which flows through the current protection of the transmission line, and causes the protection misoperation or failure action, so the penetration level of DG needs to be analyzed according to the current protection. This paper analyzes the impact of DG on the protection, when the short circuit fault occurs at different positions of the transmission line, including increasing flow, decreasing flow and the opposite direction flow. At the same time, the short circuit current calculation formula of the distribution network with DG connected is deduced. On this basis, it calculates the short circuit current flowing through the current protection. According to the protection setting values, the maximum penetration level of DG connected into distribution network is analyzed, in order to ensure the current protection correct operation.