PERFORMANCE STUDY OF A SOLAR COOLING SYSTEM WITH PTC AND A DOUBLE-EFFECT ABSORPTION CHILLER

韩崇巍,季杰,何伟,裴刚
DOI: https://doi.org/10.19912/j.0254-0096.2010.02.003
2010-01-01
Abstract:A numerical model of the solar cooling system with PTC and a double-effect LiBr/H2O absorption chiller was set up for the simulation of the system performance, and the influence of the operating temperature on the overall efficiency of the system was studied. The results show that the PTC possesses very high efficiency at high temperature; the overall efficiency of the system achieves a maximum value of 0.8250 at operating temperature of 173.5°C; the system with PTC and a double-effect LiBr/H2O absorption chiller has better system performance compared with the solar absorption cooling system with CPC or ETC; when PTC is used, its area is the least under the same design condition, but due to its high price, the system cost is still at a high level.
What problem does this paper attempt to address?