Experiment on Performance of Solar Adsorption Air Conditioning
Lu Zisheng,Wang Ruzhu,Xia Zaizhong,Dai Yanjun,Lu Xiurui,Yang Chuanbo
DOI: https://doi.org/10.3969/j.issn.0253-4339.2010.02.001
2010-01-01
Abstract:The influence of hot water inlet temperature,cooling water inlet temperature,chilled water outlet temperature,and hot water flow rate on the performance of a silica gel-water solar adsorption unit was experimentally investigated.Moreover,a prototype of the solar adsorption air conditioning was installed and measured in Dezhou city(north latitude of 36°41') in China.On a typical summer day,the average thermal efficiency of the solar collector,the average COP of the adsorption refrigerator,and the average solar COP of the system are 0.36,0.44,and 0.16,respectively.The results show that the performance rises with the increase in the hot water inlet temperature,chilled water outlet temperature,hot water flow,and solar radiation intensity,and it declines with the increase in the cooling water inlet temperature.When the hot water inlet temperature,cooling water inlet temperature,and chilled water outlet temperature were 79.0℃,25.4℃,and 13.7℃,respectively,the cooling capacity was 17.9kW and the COP was 0.63.The cooling capacity was 12.7kW and the COP was 0.42 when the hot water flow rate,hot water inlet temperature,cooling water inlet temperature,and chilled water outlet temperature were 2124kg/h,79.9℃,30.2℃,and 15.3℃,respectively.