A Fault Location Method of High Voltage Grid Transmission Line Based on Overvoltage Online Monitoring Signal

司马文霞,陈伟,杜林,袁涛,杨庆
DOI: https://doi.org/10.13296/j.1001-1609.hva.2010.06.010
2010-01-01
Abstract:With the continuous development of high voltage grid in scale,the conventional fault location method based on single line cannot satisfy requirement of fault location for whole grid.Adopting the two-terminal traveling wave location,this paper presents a graph dependent method of fault location on high voltage grid transmission lines on the basis of the over-voltage on-line monitoring signals and the systematic structure of grid.In this method,a dependency graph is built according to the alarm association relationship among all grid objects,and when a fault occurs on a transmission line in the grid,the voltage traveling wave arrival time is recorded by location device in each substation.Thereby the fault line can be found firstly according to the recorded data,and then the exact location of the fault can be calculated by combining the optimal ordered pair.The feasibility of this method is verified by simulations of real faults.
What problem does this paper attempt to address?