Research of Discharge Characteristics about Spark Gap Type Arrester
Rongzhu Wang,Jianhua Yu,Yuta Li,Yujun Qiang,Zhendong Lv,Yunfeng Zhang
DOI: https://doi.org/10.12013/qxyjzyj2016-007
2016-01-01
Abstract:Spark gap SPD is widely used in electric power system because of its advantages of high discharge capacity, large current capacity, small leakage current and so on. Based on related experiments, the paper discusses and analyzes the characteristics of the spark-gap arresters from the aspect of the distance between the gas discharge voltage and gap the electrode shape, the wave of voltage, the pressure, the temperature, the radiation, as well as the nature of gas. Through the experiment, it draws the following conclusions: 1) The the discharge gap of low-voltage power supply surge protector should be greatly reduced, the discharge gap for high voltage lines is much higher than the calculated result from U=1560+500L, which means that it should be considered to be reduced. 2) The gap of surge protective device is good in uniform electric field, with the easy volt-second curve, the small discharge dispersion, and the good protection characteristic. 3) The SF6/N2 mixed gas possesses the characteristics of high electrical resistance, low sensitivity to the uniformity of the electric field, low temperature with the liquefaction, stable chemical properties, low toxicity, low cost, etc. In the actual design of surge protector the use of the mixed gas as the spark gap insulating materials can be considered.