Calculation of the Maximum Magnetic Field Inside the Lightning Protection System of a Building

JI Ya-fei,ZHAO Ke,YANG Yu,ZOU Jun,ZHAO Jiang-he
DOI: https://doi.org/10.13336/j.1003-6520.hve.2009.04.001
2009-01-01
Abstract:EMI/EMC problems caused by a lightning struck a building are important research topics in building lightning protection area.This paper studies the calculations of the transient current distributions and the inner magnetic field of the lightning protection system (LPS) struck by lightning. The transmission line model is well established to model the LPS, and the time- frequency method is introduced to solve the model.Then, the megnetic field distribution inside building is calculated with the analytical method based on the current distribution.finally, this paper analysises and certifies the rationality and applicablity of the approximate calculation formula advocated by IEC standards from the point of view of parameter changes according to the current distribution.
What problem does this paper attempt to address?