Anti-interference in Partial Discharge Test for Current Transformer Supplied with Variable-frequency Power

Han ZHANG,Wei-dong LIU,Zhi-yang FU,Mei-yun TANG,Wen-hui LEI
DOI: https://doi.org/10.13336/j.1003-6520.hve.2009.04.032
2009-01-01
Abstract:Interference must be removed in partial discharge test for current transformer supplied with variable-frequency power source, which has the merits such as small capacity, low cost, no magnetic saturation and so on relative to conventional power frequency source. In this paper, the waveform and phase features of both radiation interference and conduction interference in high-voltage hall are analyzed. When test is conducted, the phase angel of the interference come from experimental loop is invariable while the one come from power loop is variable according to power frequency. It was achieved that the background noise in the complete set of apparatus was less than 5 pC to satisfy the requirement of PD test for 500/220 kV current transformer by the measures including filtering for conversion cabinet in variable-frequency cabinet, reforming the shield, no PD disposal for high-voltage test facility, the combination of single-point grounding and multipoint grounding, and adopting the measuring circuit with balanced method. An insulation defect of 500 kV stand upside down type oil immersed current transformer was detected by testing with this method. After reducing noise, the equal PD effect could be obtained by supplying with variable-frequency power compared to conventional power source, and the methods could be used at locale test.