Studying thermal performance of split-type airconditioners at building re-entrant via computer simulation
T. T. Chow,Z. Lin,Q. W. Wang,J. W. Z. Lu
1999-01-01
Abstract:The use of split-type air-conditioners in new apartment buildings becomes popular in Hong Kong. One requirement for their effective use is satisfactory heat rejection at the outdoor condensing units. When a group of outdoor units is working together, the heat released by one condenser may affect the heat rejection rates at the others, and hence may deteriorate their performance. At the layout-design stage, an HVAC engineer often finds it difficult to predict such a thermal effect, say, when over a hundred of these out d or units are to be placed inside one single re-entrant of a high-rise building. This paper presents a simulation approach to tackle the problem. The computation technique is demonstrated by its application to evaluate the effect of proper spacing between adjacent condensing units. INTRODUCTION Most residents of Hong Kong live in high-rise apartment buildings. New apartment buildings in the city are typically comprised of a number of residence towers standing on a common podium garden (see Figure 1). Covered car-park, shopping mall, and other supporting facilities are often found below the podium level. The floor plan of each residence tower is based on a cruciform design with its four wings radiating out from the building core. At the building core are the communal space like lift shafts, lift lobbies, corridors, meter rooms, and public stairs etc. Typically there are eight flats on a single floor, two at each wing. A narrow but deep re-entrant exists at each wing between the neighbouring flats [1]. These re-entrants provide ventilation and natural light to the kitchens and the toilets of the apartments. In recent years, split-type air-conditioners are widely adopted as a standard provision in new apartments to serve the living/dining rooms and the bedrooms. The distinct advantages of split-type units lie in the quiet operation and the flexibility in multi-room services [2]. By placing the outdoor condensing units inside the re-entrants, the provision can retain a clean and tidy external look of the building – not being spoiled by the windowmounted air-conditioners as it was used to be in the previous design. However, it is known that for split-type units, effective cooling performance of the indoor airconditioning units requires effective heat dissipation at the outdoor condensing units. For a 30-storey apartment building, it is not surprising to have over a hundred of these out door units being placed inside a single re-entrant. Heat energy released altogether brings about a natural upward flow of air. Depending on the actual layout of the outdoor units, air temperature at the upper part of the re-entrant may reach an unacceptably high level. This could in turn downgrade the air-conditioner performance because of the unsatisfactory condenser-cooling condition, or even cause accidental trip of the air-conditioners. ENERGY PERFORMNANCE OF SPLITTYPE AIR-CONDITIONERS Performance of a split-type unit can be described by its coefficient of performance (COP). The value of COP varies with the instantaneous working conditions, for instance, the room air condition and the condenser-cooling condition. An airconditioner performs better at higher room temperature (T r), and lower condenser on-coil temperature (T o). The COP of a split-type unit can be related to T o by the following linear regression equations at different room temperature conditions: